4 OF 12 PCS300 SERIES INSTALLATION GUIDE 650-321-017 08/16 ©2014 Phoenix Controls Specifications subject to change without notice. Rev. C
2.2.2 PHS300-x, PCS300-x, and PCS300-x-DOS Wiring
Figure 3. PHS300-x, PCS300-x, and PCS300-x-DOS connections
NOTE
The PHS300-x and PCS300-x do not have OVR or SET terminals and the EXT-OVR and SEN terminals are non-functional.
PHS300-x, PCS300-x, and PCS300-x-DOS Wiring with Jumper in: 4 to 20 mA Setting
Terminal Applicable to: Option Description
OVR1 and OVR2 PCS300-x-DOS
only
O Occupancy override status:
N.O. contact output (300 mA @ 24 Vdc)
SET1 and SET2 PCS300-x-DOS
only
S Temperature setpoint:
0 -20 KΩ output
SEN1 and SEN2 PCS300-x and
PCS300-x-DOS
Temperature sensor:
10K-2 thermistor output
EXT-OVR PCS300-x-DOS
only
D External "person" icon override:
Bypass control (from Phoenix valve) indication; "person" icon is solid (occupied) when
this pin is switched to power ground (see Bypass/External "Person" Icon Control on page 7 )
VOUT All Not used
V+ All Humidity sensor: 4-20 mA output
GND All 24 Vdc power (see Specifications on page 10 for details)