Installation Manual: PSS 3032 2-3
~
=
PSS 3032
L1
N
+24 V
0 V
External power supply
24 V
0 V
Functional
earth
Connect in star to the central
earth point
0 V
Connect to the 0 V mains
and earth at a single point
Supply terminal
on the inputs
Supply terminals on the
power supply
Installation
The system should be installed in an enclosure (e.g. control cabinet)
which conforms to the protection class required.
When installing the unit in an enclosure such as a control cabinet, the
technical specifications below must be taken into account:
Protection type (EN 60 529, 10/91) IP 20
Protection class (DIN VDE 0106,
Part 1/A1, 04/90) 1
Mounting position Vertical
Ambient temperature (DIN IEC 68-2-14, 06/87) 0 ... 60 °C
Storage temperature (EN 60 068-2-1/-2, 03/93) -25 ... +70 °C
Relative humidity
(DIN IEC 68-2-30, 09/86) Max. 95 % r.h.
Condensation Not permitted
Vibration (EN 60 068-2-6, 04/95) Frequency range:
10 ... 100 Hz
Amplitude:
0.1 mm, max. 5g
Shock (DIN IEC 68-2-29) 30g, 11 ms/10g, 16 ms
EMC EN 50 082-2, 03/95
EN 55 011 A, 08/96
Fig. 2-1: Supplying the system

Related product manuals