Wiring
5-12 Operating Manual: PSS(1) DI2O Z
Example: Dual-pole outputs
Features:
With dual-channel operation, the outputs may be used for applications
up to Category 4 in accordance with EN 954-1 (11/94) (depending on
the application area and its respective regulations).
Output current: 2 A
The continuous current over all the outputs must not exceed 10 A.
Where actuators are not self-monitoring, position monitoring must be
used, e.g. via a feedback loop.
Non-safe actuators must be redundant for Category 3 and Category 4.