EasyManuals Logo

Pixsys ATR 121 User Manual

Pixsys ATR 121
99 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #22 background imageLoading...
Page #22 background image
21
9
ATR121
ATR141
Offset
calibration.
This value is
added to the
process
value
visualized on
display
(usually
correcting
the ambient
temperature)
-19.9
+99.9
units
-99.9
+99.9
units
Tenths of degree
for temperature.
Digits for linear
signals and
potentiometers
(default 0.0)
10
ATR121
ATR141
Gain
calibration of
sensor input
(The
visualized
number is
multiplied for
this % value
to calibrate
process
value)
-19.9%
+99.9
%
-99.9%
+99.9%
(default 0.0)
22
Heating (N.O.)
(default)
Cooling (N.C.)
Absolute alarm
with manual
reset of contact
Absolute alarm
with manual
reset; status of
relay stored in
case of switch-
off
11
Type of
control
Heating mode
with PID set to 0
if process value
is above setpoint
value
Open contact
safety (default)
12
Type of
contact for
control
output in
case of error
Closed contact
safety
On with open
contact
13
ATR121
ATR141
State of led
OUT1
according to
relevant
contact
On with closed
contact (default)
14
ATR121
ATR141
ON/OFF
hysteresis or
dead band
for P.I.D.
control
-199…
+999
digits
-999…
+999
digits
Tenth of degree
for temperature
sensor. Digits for
linear signals
and
potentiometers
(default 0.0)