Cooling recovery function
The heat exchanger is driven on max speed to recover the
relative cold in the room when the outdoor air
temperature is higher than the exhaust air temperature.
Conditions for starting:
– No need of heating
– The outdoor air temperature is higher than the exhaust
air temperature
Conditions for stopping:
– The unit calls for heating
–The outdoor air temperature drops below the exhaust air
temperature
The text "COOL RECOVERY" flashes on the second line
on the display.
Purging function
The unit is operating but there is no need of heating and
the rotor does not operate.
After ca 3,5 hours the rotor is started during 1 minute on
max for purging.
Recooling
If the reheater has been operating, the coil is cooled off on
min. flow during 3 minutes, despite if Stop has been
ordered.
The text "RECOOLING" flashes on the second line on the
display.
Zero calibration
Every time the fans are stopped, the regulation controls
that the zero values of the pressure sensors are correct.
When the value is incorrect and the regulation carries out
a new calibration, the text "ZERO CALIBRATION" flashes
in the display. The fans are unable to start during this
time.
::::
RET PROG
1 = SVENSKA
2 = ENGLISH
8.13 Language selection
The language can be altered between SVENSKA and
ENGLISH at any time.
The alteration is carried out when return to "main menu"
is done.