EasyManua.ls Logo

Polon-Alfa IGNIS 2000 - Control Panel Functions and Access Levels

Default Icon
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IK-E339-001E 13
4.7 CONTROL PANEL FUNCTIONS AND ACCESS LEVELS
Four access levels to handling elements are provided in the control panel:
1
st
access level intended for the persons who take first measures after a fire or fault signal
occurrence. At this access level, the ACKNOWLEDGEMENT (17), FAULT (2) and DELAY RESET (5) push
buttons are active, as well as an access code entering function.
2
nd
access level is provided for persons holding special responsibility for safety who are trained and
authorised to service the control panel within a limited scope. The second access level is obtainable
by appropriate access code entering. It allows to use all the push buttons located on the device’s
front panel and functions that do not change the control panel programmed configuration.
3
rd
access level is designed for trained persons who are authorised to change the configuration data
and carry out maintenance works. The 3
rd
access level is obtained by proper access code entering.
4
th
access level is provided for persons trained and authorised by the manufacturer to change the
factory software and use the service functions. The access level is reachable by appropriate access
code entering.
Default access codes:
• 2
nd
access level – 2 0 0
• 3
rd
access level – 3 0 0
• 4
th
access level – 4 0 0
The default access codes can be changed to the user’s codes with the help of the F.11 function.
Note! The default access codes restoring can be executed by closing the 1-2 contacts of the S15
jumper located on the printed board.
Table 4.2 presents the functions that are available at the control panel menu after relevant code
entering.
Table 4.2
Function
No.
Function name
Access level required for
this function
F.01
FAULT READOUT
1
st
or 2
nd
, or 3
rd
, or 4
th
F.02
DISABLEMENTS
2
nd
or 3
rd
, or 4
th
F.03
HARDWARE TESTING
2
nd
or 3
rd
, or 4
th
F.04
EVENT READOUT
2
nd
or 3
rd
, or 4
th
F.05
STANDARD CONFIGURATION
3
rd
or 4
th
F.06
LINE CONFIGURATION
3
rd
or 4
th
F.07
RELAY PROGRAMMING
3
rd
or 4
th
F.08
DELAY SETTING
3
rd
or 4
th
F.09
EVENT MEMORY RESET
4
th