Min Outdoor Air (OA) Opening (4) is optionally equipped with a motorized damper and filter(s). The Manual
OA Damper (5) is usually used to set proper amount of outdoor air intake.
Refrigeration coils - Evaporator (7) and Reheat (internal condenser) (8) - are located directly downstream of
the Main Filter Rack (9).
o Evaporator Bypass Damper (10) is located next to the evaporator coil. It helps to control compressor
suction pressure by adjusting the amount of air, bypassing the evaporator.
Space heater (11) location, if the dehumidifier is equipped with one, may vary:
o Hot water coil is usually located directly downstream of the reheat coil;
o Electric heater may be in the same place as the hot water coil or mounted directly on the
dehumidifier’s supply air duct connection.
o Gas heater normally is installed externally.
Compressor (13), Receiver (14) and other components are located within the Compressor Compartment (3).
o If the dehumidifier has the standard pool water heating option, the compressor circuit includes the
coaxial pool water heat exchanger (15) and refrigeration pool valve.
o If the dehumidifier has the water-cooled air conditioning option (equipped with fluid cooler or
connected to external water-cooling source), the compressor circuit also includes the plate heat
exchanger (16)).
Main Electric Panel contains Main Control Board (17), Operator Panel (18) and other electrical components.