AK500 System Installation and User's Guide
Positron Access Solutions 98 Document 180-0037-003 R01
Observe local practice electrostatic discharge precautions when handling
electronic equipment. Do not hold electronic plugs by their edge. Do not touch
components or circuitry. Use a grounding wrist strap attached to grounding
connection point on the left side of the chassis. Use only ESD-protective
packaging materials when transporting equipment.
Care should be taken when installing in a closed or multi-unit rack to ensure that
the maximum operating ambient temperature of 65°C (149°F) is not exceeded.
Installation of the equipment in a rack should be such that the amount of air flow
required for safe operation of the equipment is not compromised.
Connect the unit only to a properly rated supply circuit. Reliable earthing
(grounding) of rack-mounted equipment should be maintained. Particular
attention should be given to supply connections other than direct connections to
the branch circuit (e.g. use of power strips).
During installation and service do not connect the chassis to a live power source.
Ensure that fuses are removed from the fuse panel.
This device complies with Part 15 of the FCC rules. Operation is subject to the
following two conditions: AK355 & AK5000 Product Family 3 Document 180-
0037-001 R06A
1. This device may not cause harmful interference.
2. This device must accept any interference received, including
interference that may cause undesired operation.
This product is intended for installation in Restricted Access Locations only.
Mounting of equipment in a rack should be such that a hazardous condition is not
achieved due to uneven mechanical loading.
The Positron Multi Pair span interface is designed to coordinate with a standard
300 Vdc gas discharge tube protector. Carbon block protectors shall not be used.
The 300Vdc gas tube protector shall have the performance characteristics as
follows:
- DC Breakdown Voltage (Max.) 475 V @ 2000V/sec
- Impulse Breakdown Voltage (Max.) 650 V max @ 100 V/μsec