APPENDIX B. SPECIFICATION
220V, 230V, 240V (adjustable from 149.5V to 310V)
50Hz / 60Hz ±10% auto sensing
On Battery: Pure sine wave at +/-5% nominally,
-10% after low battery warming
Output voltage boost when input voltage between -9%
to -27.5% of nominal; output voltage buck when
input voltage between +9% to +25% of nominal.
6 to 8 millisecond including detection time (typical)
UPS automatic power off if overload exceeds 110% of
nominal at 20 seconds; 125% at 5 seconds
UPS output cut off immediately or protected by
input circuit breaker
Buzzer beeps under backup mode, battery low,
battery charging fault, and overload
Sealed, maintenance-free lead acid battery
Automatic diagnostics, over-discharge and
short circuit protection by fuse
Standard - RS-232, RJ45 and USB B-type; *Optional - SNMP
<50dBA (1 meter from surface)
0 to 40℃, 0 to 95% humidity (non-condensing)
○,