Specifications
35
Powerware
®
9120 User's Guide 05147426 A Uncontrolled Copy
Table 6. Environmental and Safety
120V Models 208V Models 230V Models
Operating
Temperature
0°C to 40°C (32°F to 104°F) 01500 meters above sea level
0°C to 35°C (32°F to 95°F) 15003000 meters above sea level
Optimal battery performance: 25°C (77°F)
Storage
Temperature
-15°C to 50°C (-5°F to 131°F)
Relative Humidity 095% noncondensing
Operating
Altitude
Up to 3,000 meters (10,000 ft) above sea level
Audible Noise 7001500 VA: Less than 48 dBA Normal mode, typical load
20003000 VA: Less than 54 dBA Normal mode, typical load
Surge
Suppression
ANSI C62.41 Category B (formerly IEEE 587)
Safety
Conformance
UL 1778, UL 497A;
CAN/CSA C22.2, No. 107.1
UL 1778 (7002000 Models),
UL 497A (data line only);
CAN/CSA C22.2, No. 107.1
EN 50091-1-1 and IEC 60950;
Agency Markings UL, cUL UL, cUL, CE, C-Tick
EMC FCC Part 15, ICES-003, VCCI EN 50091-2, FCC Part 15, ICES-003
Table 7. Weights and Dimensions
UPS Models
Extended Battery Module Models
120/208V Models 230V Models
Dimensions
(WxDxH)
7001000 VA: 6.2 x 16.2 x 9.6
(15.8 x 41.2 x 24.3 cm)
1500 VA: 6.7 x 17.5 x 10.8
(17.0 x 44.4 x 27.5 cm)
20003000 VA: 8.6 x 18.6 x 14.2
(21.7 x 47.2 x 36.1 cm)
7001000 VA: 6.2 x 16.2 x 9.6
(15.8 x 41.2 x 24.3 cm)
1500 VA: 6.7 x 17.5 x 10.8
(17.0 x 44.4 x 27.5 cm)
20003000 VA: 8.6 x 18.6 x 14.2
(21.7 x 47.2 x 36.1 cm)
Weight PW9120 700: 29 lb (13.2 kg)
PW9120 1000: 35.5 lb (16.1 kg)
PW9120 1500: 46.5 lb (21.1 kg)
PW9120 2000: 82 lb (37.2 kg)
PW9120 3000: 89 lb (40.5 kg)
PW9120 3000H: 89 lb (40.5 kg)
PW9120 3000B: 85 lb (38.5 kg)
PW9120 700i: 28 lb (12.6 kg)
PW9120 1000i: 34 lb (15.3 kg)
PW9120 1500i: 44 lb (19.8 kg)
PW9120 2000i: 81.6 lb (37 kg)
PW9120 3000i: 85 lb (38.5 kg)
PW9120 BAT-700: 31 lb (14 kg)
PW9120 BAT-1000: 44 lb (20 kg)
PW9120 BAT-1500: 57 lb (26 kg)
PW9120 BAT-3000: 110 lb (50 kg)