Model cont. 40-8 50-6 60-7 75-9 100-12
Rated Heat Capacity
kW 40.0 50.0 60.0 75.0 100.0
Low Heat Input
Nett CV kW 24.2 30.2 36.3 45.3 60.4
Minimum Heat Capacity
kW 21.6 26.5 31.7 39.9 53.3
Useful Efficiency
High Fire % 91% 91% 91% 91% 91%
Low Fire % 89% 88% 87% 88% 88%
Electrical Power Consumption*
High Fire kW 0.07 0.07 0.07 0.07 0.07
Low Fire kW 0.07 0.07 0.07 0.07 0.07
Standby kW <0.01 <0.01 <0.01 <0.01 <0.01
Ignition kW
0.00 0.00 0.00 0.00 0.00
NOx Seasonal (Gross)
mg/kWh
163.2 129.6 157.6 147.1 149.3
Envelope Loss Factor
% n/a n/a n/a n/a n/a
Emission Effiency
% hs, flow 93.3% 94.7% 94.8% 94.4% 94.0%
Seasonal Space Heating Energy Efficiency
% hs,h 72.02% 72.01% 72.01% 72.08% 72.04%
Apendix 1: Information required for ecodesign (ErP) Directive 2009/125 - HEM NVx
Model cont. 110-13 125-15 150-18 175-21 200-24
Rated Heat Capacity
kW 110.0 125.0 150.0 175.0 200.0
Low Heat Input
Nett CV kW 66.5 75.6 90.7 105.8 120.9
Minimum Heat Capacity
kW 58.7 66.7 80.0 93.3 106.7
Useful Efficiency
High Fire % 91% 91% 91% 91% 91%
Low Fire % 88% 88% 88% 88% 88%
Electrical Power Consumption*
High Fire kW 0.07 0.07 0.07 0.07 0.07
Low Fire kW 0.07 0.07 0.07 0.07 0.07
Standby kW <0.01 <0.01 <0.01 <0.01 <0.01
Ignition kW
0.00 0.00 0.00 0.00 0.00
NOx Seasonal (Gross)
mg/kWh
149.3 149.3 149.3 149.3 149.3
Envelope Loss Factor
% n/a n/a n/a n/a n/a
Emission Effiency
% hs, flow 93.9% 93.9% 94.0% 93.7% 93.7%
Seasonal Space Heating Energy Efficiency
% hs,h 72.05% 72.06% 72.03% 72.01% 72.01%
Model 10-3 15-4 18-5 25-5 30-6
Rated Heat Capacity
kW 10.0 15.0 18.0 25.0 30.0
Low Heat Input
Nett CV kW 6.0 9.0 10.9 15.1 18.1
Minimum Heat Capacity
kW 5.4 8.0 9.6 13.4 16.0
Useful Efficiency
High Fire % 91% 91% 91% 91% 91%
Low Fire % 89% 89% 88% 89% 88%
Electrical Power Consumption*
High Fire kW 0.07 0.07 0.07 0.07 0.07
Low Fire kW 0.07 0.07 0.07 0.07 0.07
Standby kW <0.01 <0.01 <0.01 <0.01 <0.01
Ignition kW
0.00 0.00 0.00 0.00 0.00
NOx Seasonal (Gross)
mg/kWh
149.3 157.1 149.3 170.8 153.3
Envelope Loss Factor
% n/a n/a n/a n/a n/a
Emission Effiency
% hs, flow 95.1% 94.4% 94.8% 94.8% 94.2%
Seasonal Space Heating Energy Efficiency
% hs,h 72.02% 72.01% 72.01% 72.07% 72.06%