Section V Control panel and operation
15
distance is allow to be more than 3 m.
5-1-11. Keyboard digital display illustration
Display
letter
relative
letter
Display
letter
relative
letter
Display
letter
relative
letter
0
1
2
3
4
5
6
7
8
9 g
A R
B
C
d D
E
F
H
J
L
N
U V
o
P
r
Y
RUN
Ver
READY
good
Err
M
N
5-2 Function parameters setting and description
Function parameters code in the following table
Code Setting Description
Code
Name
Range
of set
value
Factory
setting
Explanation
P0
Starting voltage
30-70%
30%
Voltage slope model is effective, the
starting voltage of current mode is
40%.
P1
Soft starting time
2-60S
16S
Limiting current mode does not
work.
P2
Soft stop time
0-60S
0S
Setting 0 means free stopping, please
set 0 for one with two onnections .
P3
Start delay
0-999S
0S
With a countdown delay, set to 0
without delay, starting immediately.
P4
Language selection
01
0
0 for Chinese display, 1 for the
English display.
P5
Starting current limit
50-
500%
280%
The current limiting mode is
effective; the maximum flow value
of the voltage slope mode is 400%.
P6
Load regulation rate
50-
200%
100%
Relative to the value of the rated
current PP.
P7
Under voltage
protection
40-
90%
80%
Protection below the set value.

Table of Contents