10
Zenex Plus User Manual
HZ INTEGRAL TIME >>
0 to 3600 sec
(Default : 100 sec)
Integral Time for
Heat Pre-dominant zone
HZ DERIVATIVE TIME >>
0 to 600 sec
(Default : 16 sec)
Derivative Time for
Heat Pre-dominant zone
CYCLE TIME >>
0.5 to 100.0 sec
(Default : 10.0 sec)
OVERSHOOT INHIBIT >>
Enable
Disable
(Default : Disable)
CUTOFF FACTOR >>
1.0 to 2.0 sec
(Default : 1.2 sec)
OVERSHOOT INHIBIT >>
Enable
Disable
(Default : Disable)
CUTOFF FACTOR >>
1.0 to 2.0 sec
(Default : 1.2 sec)
OVERSHOOT INHIBIT >>
Enable
Disable
(Default : Disable)
CUTOFF FACTOR >>
1.0 to 2.0 sec
(Default : 1.2 sec)
PROPORTIONAL BAND >>
0.1 to 999.9
(Default : 50.0)
INTEGRAL TIME >>
0 to 3600 sec
(Default : 100 sec)
DERIVATIVE TIME >>
0 to 600 sec
(Default : 16 sec)
PROPORTIONAL BAND >>
0.1 to 999.9
(Default : 50.0)
INTEGRAL TIME >>
DERIVATIVE TIME >>
0 to 3600 sec
(Default : 100 sec)
0 to 600 sec
(Default : 16 sec)
CZ PROP BAND >>
0.1 to 999.9
(Default : 50.0)
Proportional Band for
Cool Pre-dominant zone
CZ INTEGRAL TIME >>
0 to 3600 sec
(Default : 100 sec)
Integral Time for
Cool Pre-dominant zone
CZ DERIVATIVE TIME >>
0 to 600 sec
(Default : 16 sec)
Derivative Time for
Cool Pre-dominant zone
Heat Only Control
Heat + Cool
Control Zone : Single
Heat + Cool
Control Zone : Dual
HZ PROP BAND >>
0.1 to 999.9
(Default : 50.0)
Proportional Band for
Heat Pre-dominant zone
CYCLE TIME >>
0.5 to 100.0 sec
(Default : 10.0 sec)
CYCLE TIME >>
0.5 to 100.0 sec
(Default : 10.0 sec)