14 5333V111-UK
5333QA01
LERBAKKEN 10, 8410 RØNDE DENMARK. WWW.PRELECTRONICS.COM
Revision date:
2013-08-07
Version Revision
V2R0
Page:
2/2
Installation notes:
In a potentially explosive gas atmosphere, the transmitter shall be mounted in an enclosure in
order to provide a degree of protection of at least IP20 according to EN60529.
If the transmitter is installed in an explosive atmosphere requiring the use of equipment of
category 1 G, 1 M or 2 M, and if the enclosure is made of aluminum, if must be installed such,
that ignition sources due to impact and friction sparks are excluded.
If the enclosure is made of non-metallic materials, electrostatic charging shall be avoided.
For installation in a potentially explosive dust atmosphere, the following instructions apply:
The transmitter shall be mounted in a metal enclosure form B that is providing a degree of
protection of at least IP6X according to EN60529, that is suitable for the application and
correctly installed.
Cable entries and blanking elements shall be used that are suitable for the application and
correctly installed.
For an ambient temperature 60ºC, heat resistant cables shall be used with a rating of at least
20 K above the ambient temperature.
The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a
dust layer with a thickness up to 5 mm