5714V104-UK 19
REL1
SET --> ENTER RELAY 1 SETUP
SKIP --> SKIP RELAY 1 SETUP
OFF --> RELAY 1 DISABLED
SETP
xxxx --> RELAY SETPOINT
ACT1
INCR --> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNALL
HYS1
xxxx --> RELAY HYSTERESIS
ERR1
HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx --> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx --> RELAY OFF-DELAY IN SECONDS
REL2
SET --> ENTER RELAY 2 SETUP
SKIP --> SKIP RELAY 2 SETUP
OFF --> RELAY 2 DISABLED
SETP
xxxx --> RELAY SETPOINT
ACT2
INCR --> ACTIVATE AT INCREASING SIGNAL
DECR --> ACTIVATE AT DECREASING SIGNAL
HYS2
xxxx --> RELAY HYSTERESIS
ERR2
HOLD --> HOLD RELAY AT ERROR
ACTI --> ACTIVATE RELAY AT ERROR
DEAC --> DEACTIVATE RELAY AT ERROR
NONE --> UNDEFINED STATUS AT ERROR
ON.DE
xxxx --> RELAY ON-DELAY IN SECONDS
OF.DE
xxxx --> RELAY OFF-DELAY IN SECONDS
A.OUT
0-20 --> OUTPUT RANGE IN mA
4-20 --> OUTPUT RANGE IN mA
20-0 --> OUTPUT RANGE IN mA
20-4 --> OUTPUT RANGE IN mA
O.LO
xxxx --> DISPLAY VALUE FOR OUTPUT LOW
O.HI
xxxx --> DISPLAY VALUE FOR OUTPUT HIGH
O.ERR
23 mA --> NAMUR NE43 UPSCALE AT ERROR
3,5 mA --> NAMUR NE43 DOWNSCALE AT ERROR
0mA --> DOWNSCALE AT ERROR
NONE --> UNDEFINED OUTPUT AT ERROR
RESP
xxx.x --> ANALOGUE OUTPUT RESPONSE TIME
IN SECONDS
E.PAS
NO --> ENABLE PASSWORD PROTECTION
YES
N.PAS
xxxx --> SELECT NEW PASSWORD
ADV MENU:
LANG --> ENTER LANGUAGE SETUP
DISP --> ENTER DISPLAY SETUP
CAL --> PERFORM PROCESS CALIBRATION
HLP.T
DE --> DE - WAEHLE DEUTSCHEN HILFETEXT
DK --> DK - VAELG DANSK HJAELPETEKST
ES --> ES - SELECCIONAR TEXTO DE
AYUDA EN ESPANOL
FR --> FR - SELECTION TEXTE D’AIDE
EN FRANCAIS
IT --> IT - SELEZIONARE TESTI DI
AIUTO ITALIANI
SE --> SE - VALJ SVENSK HJALPTEXT
UK --> UK - SELECT ENGLISH HELPTEXT
CZ --> CZ - VYBER CESKOU NAPOVEDU
LIGH
xxxx --> ADJUST DISPLAY LIGHT INTENSITY
CA.LO
YES --> CALIBRATE INPUT LOW TO PROCESS
VALUE?
NO
CA.HI
YES --> CALIBRATE INPUT HIGH TO PROCESS
VALUE?
NO
VAL.L
xxxx --> SET VALUE FOR LOW CALIBRATION
POINT
VAL.H
xxxx --> SET VALUE FOR HIGH CALIBRATION
POINT
USE.C
YES --> USE PROCESS CALIBRATED VALUES?
NO