34 9106 - Product Version 9106-001
9106QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2011-11-02
Version Revision
V3 R0
Prepared by:
PB
Page:
3/5
9106B1A, 9106B1B, 9106B2A, 9106B2B
Ex input : External current source
CH1 (terminal 41,42)
CH2 (terminal 51,52)
U
o
: 0 V
I
o
: 0 mA
P
o
: 0 mW
U
i
: 30 V
I
i
: 120 mA
P
i
: 0.85 W
C
i
: 2 nF
L
i.
0 μH
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9106
4501
91 92 93 94 95
Power
Rail
CH1
CH2
+
+
_
_
-20 Ta +60ºC
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m
: 253 V, max. 400 Hz
Simple Apparatus or
Intrinsic safe apparatus
with entity parameters:
Vmax (Ui) Vt (Uo)
Imax (Ii) It (Io)
Pi ≥ Pt (Po)
Ca ≥ C
cable + Ci
La ≥ L
cable + Li
Hazardous Classified Location Unclassified Location or
Class I/II/III, Division 1, Group A,B,C,D,E,F,G Hazardous Classified Location
Zone 0,1, 2 Group IIC, IIB, IIA or Class I, Division 2, Group ABCD T4
Zone 20, 21 Class I Zone 2 Group IIC T4