Page 45
Addr. of Modbus register Data stored in memory with the 0x0020 command
41001-41002 Cells capacity
41003 Cells sensitivity
41004 Weight division value
41005-41006 Tare of the system
41007-41008 System capacity
41101 Weight filter
41102 Weight stability
41103-41104 Auto-zero setpoint
41105 Zero tracking
41106 Zero band in divisions
41201 Operation mode Set 1
41202-41203 Hysteresis Set 1
41204 Timer Set 1
41205 Delay Set 1
41206 Operation mode Set 2
41207-41208 Hysteresis Set 2
41209 Timer Set 2
41210 Delay Set 2
41401-41402 Analog full scale
41403 Analog mode
41404 Analog range
TABLE F - WEIGHT SETPOINT OPERATION CODING
bit Setpoint operation mode
0…1 0 = Net weight, 1 = Gross weight, 2 = Peak
2 0 = N.O. 1 = N:C.
3 0 = Positive values 1 = Negative values
4 0 = Always controlled 1 = Only with stable weight
EXAMPLE: CALIBRATION FUNCTION VIA MODBUS
To perform the calibration of full scale (that require the weight value in the sample set in the data register),
the value in the data register must be present when the command register is programmed. For example:
Calibrate the full scale using a sample weight of 2000 kg.
Write 2000 in the data register.
Write 0x0011 in the command register.
Use the multiple registers write function and write the registers of data register and command register
in a single command.