7
Packaged and Split Rooftop Ventilator
© 2021 Mitsubishi Electric US, Inc.
Installation - Packaged DX
Typical Unit Weights and Dimensions
Model
Nominal
tonnage
(tons)
Height
(H)
Width
(W)
Length
(L)
Intake
(A)
Condensing
Section
(B)
Nominal
weight (lbs)
Outdoor
Intake
Supply
Discharge
Return
Intake
Exhaust
Discharge
MP-0-1 3-7 58.1 44.0 82.2
9
22.3 NA 1,180
End
Bottom
or
Side
Bottom or
End
2
NA
MP-1-1 5-15 59.3 52.5 98.6
6
/149.5
7
22.1 30.1 2,700
Bottom,
End
2
or
Side
1
End
3
or
Side
1
MP-2-1 15-30 72.5 68.2 109
6
/163.2
7
27.7 30.1 4,500
MP-4-1 25-50 101.3 98 155.2
6
/188
4
39/47.5
8
NA 6,500
Bottom,
End
11
or
Side
1
End
MP-5-1
30-70 99.5 96 185 45.3 NA 7,950
Bottom or
End
10
Side
MPE-1-1
5-15 59.3 52.5 149.5/180.5
4
22.1 30.1 3,400
End
Bottom
or
Side
Bottom,
End
2
or
Side
1
End
3
or
Side
1
MPE-2-1 15-30 72.5 68.2 163.2/197.2
4
27.1 30.1 5,100
MPE-4-1 25-50 101.3 98 199.6
5
/233.8
4
47.5 NA 8,000
Bottom or
Side
End
MPE-5-1
30-70 99.5 96 263
5
/307
4
45.3 NA 10,450 Side
All dimensions are shown in inches. Weight is shown in pounds and includes largest supply and exhaust fans, PDX with reheat, largest indirect-gas
red furnace, and all dampers. Actual weights will vary based on the unit conguration.
1
Only available with powered exhaust
2
Only available without barometric relief
3
Only available with barometric relief
4
Length with side return
5
Length with bottom return
6
Length with bottom or end return
7
Length with powered exhaust
8
Length with powered exhaust bumpout
9
Optional indirect gas-fired furnace bumpout
length is additional 13.3 inches
10
Only available without powered exhaust
11
Only available without powered exhaust and
without barometric relief