CONTROL FUNCTIONS
31
Protective functions
Compressors stops when:
High pressure exceeds 108 bar.
Restarts with manual reset.
Low pressure is below 15 bar.
Automatic reset.
BLDC Power + Alarm. See display information. Compressor
auto reset.
5 times before alarm becomes manual.
Compressor out of envelope alarm. Compressor auto reset.
5 times before alarm becomes manual.
EC Gas cooler fan is protected by internal temperature sensor.
Automatic reset.
All alarms are visible after pressing the flashing red warning triangle.
Hold down to reset. Example here: suction pressure probe broken or
disconnected.
Alarm list
A complete list of controller alarms can be found on appendix 2.