Operations4
EN9
Battery
shutdown
voltage setting
Battery type
Setting Items Icons Description
Setting range is from 10.0VDC to 11.0VDC for 12VDC
model and 20.0VDC to 22.0VDC for 24VDC model.
Low cut-o voltage will be fixed to setting value no
matter what percentage of load is connected.
Available options in 12VDC model :
10.0VDC (default)/10.2VDC/10.4VDC/10.6VDC/
10.8VDC/11.0VDC.
Available options in 24VDC model :
20.0VDC (default)/20.4VDC/20.8VDC/21.2VDC/
21.6VDC/22.0VDC.
User defined
AGM (default)
AC CHGbulk/floating:
14.2VDC/14.2VDC12VDC model default
28.4VDC/28.4VDC24VDC model default
After this option is selected, items 06 & 07 will take
eect
Flooded
Bulk charging
(C.V voltage)
voltage
Floating
charging
voltage
Recover
manufactory
setting
12VDC Model:14.2VDC (default)
24VDC Model:28.4VDC (default)
If self-defined is selected in program 05, this
program can be set up. Setting range is from 13.0VDC
to 14.6VDC for 12VDC model and increment of each click
is 0.1VDC. Setting range is from 26.0VDC to 29.2VDC for
24VDC model and increment of each click is 0.2VDC.
12VDC Model:13.7VDC (default)
24VDC Model:27.4VDC (default)
If self-defined is selected in program 05, this program
can be set up. Setting range is from 13.0VDC to 14.6VDC
for 12VDC model and increment of each click is 0.1VDC.
Setting range is from 26.0VDC to 29.2VDC for 24VDC
model and increment of each click is 0.2VDC.
Enable/Disable (default)
Recover disable
(default)
Recover