0: Heat 1 – O, Heat 2 – O
1: Heat 1 – On, Heat 2 – O
2: Heat 1 – O, Heat 2 – On
3: Heat 1 – On, Heat 2 – On
SettingsMenu Value
10
11
12
13
Temperature sensor
0: Internal Sensor
1: NTC external sensor
7
DC(Door Contact)
Fan switch of delay
Fan switch of delay,
Time, sec
Valve Heat Status on
Low Fan Speed
0: Heat 1 – O, Heat 2 – O
1: Heat 1 – On, Heat 2 – O
2: Heat 1 – O, Heat 2 – On
3: Heat 1 – On, Heat 2 – On
14
Valve Heat Status on
Med Fan Speed
0: Heat 1 – O, Heat 2 – O
1: Heat 1 – On, Heat 2 – O
2: Heat 1 – O, Heat 2 – On
3: Heat 1 – On, Heat 2 – On
15
Valve Heat Status on
High Fan Speed
0: Inactive
1: Active
0: Inactive
1: Active
60-250 sec
Modbus ID setting
1~247 (01~F7)9
Temperature delta
8
Temperature range of
antifreeze
5
Antifreeze status
0: On
1: O
6
+1 ... +5°C
+5 ... +15°C