15
4.3 Grounding
Grounding cables shall be 10AWG or higher yellow-green cables. After
connection, the resistance from battery grounding point to Ground connection
point of room or installed place shall smaller than 0.1Ω.
1) based on metal directly touch between the module’s
surface and rack’s surface. If using painted rack the
corresponding place shall remove the painting.
2) install a grounding cable to the grounding point of the
modules.

Other manuals for Pylontech US3000C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pylontech US3000C and is the answer not in the manual?

Pylontech US3000C Specifications

General IconGeneral
Battery TypeLithium Iron Phosphate (LiFePO4)
Nominal Voltage48V
Capacity74Ah
Discharge Current (Recommended)37A
Discharge Current (Maximum)74A
CommunicationCAN, RS485
Cycle Life6000 Cycles @ 25°C
Operating Temperature-10°C to 50°C
ScalabilityUp to 16 units in parallel
CertificationCE, UN38.3