Rev 3.1 01/11/23 - 33 - Model 600 User Guide
Function Code
Register
Description
Read/
Write
Type Default
Notes
Non-volatile
1122 Stage Min Off Secs RW word
120
30-600 Seconds
Y
Alarm Settings
1200 High temperature level 2 RW word 90 70-140 = degrees Y
1201
High temperature level 1
RW
word
85
70-140 = degrees
Y
1202 Low temperature level RW word 50 20-60 = degrees Y
1203
High Humidity Alarm
RW
word
0
0-100 = %RH (0 disables)
Y
1204 HVAC Lockout RW word 0
Enumerated: Y
0 = disable,
1 = normally open (closure alarms),
2 = normally closed (open alarms)
1205 Smoke Alarm input RW word 0
Enumerated: Y
0 = disable,
1 = normally open (closure alarms),
2 = normally closed (open alarms)
1206 Hydrogen Gas Alarm Input RW word 0
Enumerated: Y
0 = disable,
1 = normally open (closure alarms),
2 = normally closed (open alarms)
1207 Generator Run Alarm Input RW word 0
Enumerated: Y
0 = disable,
1 = normally open (closure alarms),
2 = normally closed (open alarms)
Misc.
1300
Product ID
RO
word
600
600
N
1301 Firmware Revision RO word
A.B.C.D in 4-bit numbers N
1302 Reset RW word
Must write 57005 to data register
for reset
N