Rev 3.1 01/11/23 - 32 - Model 600 User Guide
Register
Type Default
Non-volatile
1013 Front Panel Program Menu Lockout RW word 0 0 = allow, 1 = don't allow Y
Local Setpoints
Holding Register
(FC3/6/16)
1100 Cooling Setpoint RW word 80 60-110 degrees Y
1101 Econ Setpoint RW word 75 60-110 degrees Y
1102 Comfort Mode Cooling delta RW word 5 1-20 degrees Y
1103 Cooling off delta RW word 2 1-20 degrees Y
1104 Heating Setpoint RW word 55 30-70 degrees Y
1105 Comfort Mode Heating Delta RW word 10 1-20 degrees Y
1107 %RH control off delta RW word 20 2-50%RH Y
1108 Dehumidify Cool SPT RW word 65 60-110 Y
1109 Dehumidify Heat SPT RW word 65 30-70 Y
1110 Cool stage 2 delta RW word 2 1-10 degrees Y
1111 Cool stage 3 delta RW word 2 1-10 degrees Y
1114 OSA L2 SPT RW word 65 45-90 degrees Y
1116 L1/L2 Max Change RW word
1117 OSA Dwell Seconds RW word
1118 RH Econ Disable SPT RW word
0-100 percent, 0 = disable
1119 Comfort Mode Minutes RW word
0-240 Minutes, 0 = disable
1120 Lead Switch Hours RW word
1121 Stage Min On Secs RW word