9
FAULT DIAGNOSIS
Symptom
Cause/Rectification
1. All outlets do not
operate
(e.g. washbasin,
shower, urinal,
W.C).
a. Check power to Pulse control box (power light illuminated
on PCB).
b. If there is power to the control box, check fuse in
transformer.
2. Individual outlets
do not operate.
3. Outlets continue
running or run for
excessive
periods
a. Plug in hand held programmer and check timing for
outlet. Reprogram if necessary.
b. Check solenoid valve. Maintain or replace parts if
required.
4. Outlets only run
for a short period
of time.
a. Check output fuse on PCB. Replace as necessary.
b. Plug in hand held controller and check that non operating
outlet is set up correctly.
c. Plug in hand held controller and complete a system info
'error' check. This will identify if the sensor or solenoid
is incorrectly installed or faulty. Replace parts or products
as required.
d. Check solenoid. Replace if necessary.
a. Plug in hand held programmer and check timing for
outlet. Reprogram if necessary.
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the rada Pulse and is the answer not in the manual?

rada Pulse Specifications

General IconGeneral
Product TypeElectronic Faucet
Power SupplyBattery
ActivationInfrared Sensor
MaterialBrass
InstallationDeck Mount
Warranty5 years
Water SupplyMixed
Flow Rate3.7 l/min

Related product manuals