2. MAINTENANCE
CODE FAULT POSSIBLE CAUSE SOLUTION RESET
E02 WATER TEMP. HIGHT
LIMIT SWITCH
THERMOSTAT CABLE
DISCONNECTED;
CHECK THE WIRING: MANUAL RESET
(PRESS THE RESET
‘
’ KEY).
BROKEN HIGH LIMIT. REPL ACE IT.
E03 EXHAUST SAFETY HIGH
LIMIT SWITCH
HIGH LIMIT BROKEN; REPL ACE IT; MANUAL RESET
(PRESS THE RESET
‘
’ KEY).HIGH LIMIT CABLE
DISCONNECTED.
CHECK THE WIRING.
E04 LOW WATER CUTOFF
INSUFFICIENT WATER
PRESSURE INSIDE THE SYSTEM
[LOWER THAN 4.3
psi
(0.3
bar
)]
LOAD THE SYSTEM; AUTOMATIC.
WATER PRESSURE SWITCH
CABLE DISCONNECTED;
CHECK THE WIRING;
WATER PRESSURE SWITCH
BROKEN.
REPL ACE IT.
E05 DOMESTIC INLET
TEMPERATURE
BROKEN OR INCORRECTLY
CALIBRATED PROBE
(RESISTANCE VALUE 10
KOHM AT 77°F (25 °C) NTC);
REPL ACE IT; AUTOMATIC.
DISCONNECTED OR WET
PROBE CONNECTOR.
CHECK THE WIRING.
E06 DOMESTIC INLET
TEMPERATURE PROBE
BROKEN OR INCORRECTLY
CALIBRATED PROBE
(RESISTANCE VALUE 10
KOHM AT 77°F (25 °C) NTC);
REPL ACE IT; AUTOMATIC.
DISCONNECTED OR WET
PROBE CONNECTOR.
CHECK THE WIRING.
E15 RETURN PROBE BROKEN OR INCORRECTLY
CALIBRATED PROBE
(RESISTANCE VALUE 10
KOHM AT 77°F (25 °C) NTC);
REPL ACE IT; AUTOMATIC.
DISCONNECTED OR WET
PROBE CONNECTOR.
CHECK THE WIRING.