Radijator Inženjering d.o.o, 36000 Kraljevo, Živojina Lazića - Solunca br.6, Srbija
tel. +381 36 399 140, fax. +381 36 399 150, http://www.radijator.rs
e-mail: radijator@radijator.rs
37
Take into account the required minimum space required for access and
security elements to carry out cleaning operations
Determine whether the degree of electrical protection is in accordance with
the characteristics of the room where the boiler will be located
No exposure to atmospheric influences. The boiler itself is not anticipated for
outdoor use and contains no anti-freeze system.
It is forbidden to close the vents in the boiler room in which the openings are
necessary for proper combustion.
3.3 Connection to the chimney
The boiler TKAN works on forced draft, but the rules should be respected as if the
selection of the chimney were for the boiler working on over-pressure in the
combustion chamber some other fuel, like oil fuel, for example. Otherwise the
problems may occur in the work, especially in the ignition phase and in the mode of
solid fuel.
It is recommended that the diameter of the chimney is at least equal to the diameter
of the flue has, and minimum height of 7 to 8 meters, depending on the coverage of
the chimney by some other high buildings next to it.
The most optimal positioning of the boiler onto the flue outlet is such that connecting the
center of the exit gases from the boiler flue and chimney connection to the center is slightly
raised ( up to 3 % ) ( see Figure 7).