Approvals
Description
These kits are for use with Raychem IceStop, XL-Trace and HWAT heating
cables. The connection is designed to be strapped to the pipe or mounted
on the wall at the start of the heating cable circuit. These installation
instructions should be used in conjunction with the IceStop, XL-Trace
and HWAT System Installation and Operation Manuals. For technical
support, contact your Tyco Thermal Controls representative or call Tyco
Thermal Controls (800) 545-6258.
Tools Required
• Utility knife • Wire cutters
• TORX
®
T20 screw driver • Wrenches (2)
Additional UL Listed or CSA Certified materials required:
• 1/2-inch conduit and fittings • Junction box
Optional Accessories (not included in this kit):
• RayClic-SB-02 Wall mounting bracket
RayClic
®
F
M
APPROVED
with HWAT, IceStop,
and XL-Trace heating
cables.
CL I, Div. 2, Gr. A,B,C,D
Hazardous Locations
with GM-XT only.
WARNING:
Do not open while energized
Shock Hazard
718K Pipe Heating Cable
also Listed De-icing and
Snow Melting Equipment
-W
A B C ED F
A B C ED F
A B C ED F
G
G
G
This component is an electrical device that must be
installed correctly to ensure proper operation and to
prevent shock or fire. Read these important warnings
and carefully follow all the installation instructions.
• Tominimizethedangeroffirefromsustainedelectrical
arcing if the heating cable is damaged or improperly
installed, and to comply with the requirements of Tyco
Thermal Controls, agency certifications, and national
electrical codes, ground-fault equipment protection
must be used. Arcing may not be stopped by conven-
tional circuit breakers.
• Buswireswillshortiftheycontacteachother.Keep
bus wires separated.
• Keepcomponentsandheatingcableendsdrybefore
and during installation.
• Theblackheatingcablecoreisconductiveandcan
short. It must be properly insulated and kept dry.
• Componentapprovalsandperformancearebasedon
the use of Tyco Thermal Controls-specified parts only.
Do not use substitute parts or vinyl electrical tape.
• Leavetheseinstructionswithenduserforreference
and future use.
A B C ED F
A B C ED F
A B C ED F
G
G
G
A B C ED F
A B C ED F
A B C ED F
G
G
G
RayClic Connection System
RayClic-PCPowerConnectionandEndSealKit
RayClic-PSPoweredSpliceandEndSealKit
RayClic-PTPoweredTeeandEndSealKit
Installation Instructions
RayClic-PSPoweredSpliceKit
Item Qty Description Item Qty Description
A 1 Powered splice D 2 Clips
B 1 Pipe mounting bracket E 2 End seals
C 2 Plastic cable ties F 4 Labels
(1 HWAT, 1 De-Icing &
Snow Melting, 2 Warning)
G 1 Cable lubricant
RayClic-PTPoweredTeeKit
Item Qty Description Item Qty Description
A 1 Powered splice D 3 Clips
B 1 Pipe mounting bracket E 3 End seals
C 2 Plastic cable ties F 4 Labels
(1 HWAT, 1 De-Icing &
Snow Melting, 2 Warning)
G 1 Cable lubricant
KitContents
RayClic-PCPowerConnectionKit
Item Qty Description Item Qty Description
A 1 Power connection D 1 Clip
B 1 Pipe mounting bracket E 1 End seal
C 2 Plastic cable ties F 4 Labels
(1 HWAT, 1 De-Icing &
Snow Melting, 2 Warning)
G 1 Cable lubricant
718K Pipe Heating Cable
877Z De-Icing and Snow Melting
Not UL Listed with XL-Trace
heating cable for buried piping.
APPROVED
-w
For HWAT, IceStop, and XL-Trace only
Hazardous Locations: For IceStop (GM-XT) only
Class I, Div. 2, Groups A,B,C,D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Raychem RayClic-PC and is the answer not in the manual?

Raychem RayClic-PC Specifications

General IconGeneral
Voltage600 V
Operating Voltage600 V
Shrink RatioNot applicable
Voltage Rating600V
ColorBlack
MaterialPolymer