EasyManua.ls Logo

Raypak 503-2003 - Field Wiring Connection

Raypak 503-2003
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION C: Installation
20
CIRCUIT
BREAKER
WHITE
GROUND
BLACK
GREEN
ABC
Fig. 17: Wiring Connections
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX
AB = 108 VAC Minimum, 132 VAC MAX
BC = <1 VAC Maximum
Fig. 18: Multi-meter
Making the Electrical Connections
Refer to Fig. 16-19.
1. Verify that circuit breaker is properly sized by
referring to heater rating plate. A dedicated circuit
breaker should be provided.
2. NOTE: Current draw noted on rating plate does
not include pump current.
3. Turn off all power to the heater. Verify that power
has been turned off by testing with a multi-meter
prior to working with any electrical connections or
components.
4. Observe proper wire colors while making electri-
cal connections. Many electronic controls are
polarity sensitive. Components damaged by im-
proper electrical installation are not covered by
warranty.
5. Provide overload protection and a disconnect
means for equipment serviceability as required by
local and state code.
6. Install heater controls, thermostats, or building
management systems in accordance with the appli-
cable manufacturers’ instructions.
7. Conduit should not be used as the earth ground.
NOTICE: A grounding electrode conductor shall be
used to connect the equipment grounding conductors,
the equipment enclosures, and the grounded service
conductor to the grounding electrode.
Field Wiring Connection
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause im-
proper and dangerous operation. Verify proper
operation after servicing.
DANGER: SHOCK HAZARD
Make sure electrical power to the heater is discon-
nected to avoid potential serious injury or damage to
components.
Fig. 19: Wiring Location

Related product manuals