EasyManua.ls Logo

Raypak B0507 - Page 48

Raypak B0507
57 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TEMPERATURE CONTROL
48
Checking or Adjusting RWF55 ‘Parameter (PArA) Level’ Parameters
NOTE: Incorrect setting of the parameters in this menu may cause the water heater to malfunction. Advice should
be sought from a Raypak representative prior to using a setting other than that given in the tables.
1. Press and release ‘ENTER’, OPr appears in the lower display.
2. Press and release the down button (▼), „PArA‟ appears in the lower display.
3. Press and release ‘ENTER’; „Pb 1‟ and its value are displayed.
4. Press and release ‘ENTER’; „Pb 1‟ will start flashing
5. Press and release () or () to enter the value for the relevant parameter as shown in the Raypak Setting‟
column of the "RWF55 Parameter (PArA) Level Parameters" table on page 46.
6. Press and release ‘ENTER’ to accept the new setting.
7. Press and release (▼) to advance to the next parameter.
8. Perform steps 4 6 for each parameter. When the last „Parameter Level‟ parameter has been set, proceed to
step 9.
9. Press and hold ‘ESC’ for more than 2 seconds. The display will revert to show the probe and set point
temperatures.
Adjusting ‘Configuration (ConF) Level’ Parameters
There are 8 menus within the ConF level, each menu contains a number of sub-menus and each sub menu
contains a number of parameters. Only the menus and parameters which use a Raypak setting which differs from
the Siemens default setting are listed in the "RWF55 Configuration (ConF) Level Parameters" table on page 47.
NOTE: Incorrect setting of the parameters in this menu may cause the water heater to malfunction. Advice should
be sought from a Raypak representative prior to using a setting other than that given in the tables.
To select a menu
1. Press ‘ENTER’, „OPr‟ appears in the lower display.
2. Press and release the down button (▼) twice, „ConF‟ appears in the lower display.
3. Press and release ‘ENTER’. „InP‟ is shown on the display.
4. Press and release the down button (▼) to scroll through the various menus, „InP‟ → ‟Cntr‟ → ‟rAFC‟ → „AF‟
„OutP‟ → „binF‟ → „diSP‟ → „IntF‟.
To select a sub menu and adjust parameters.
5. Once the required menu has been selected in step 4, press and release ‘ENTER’. The first submenu will be
displayed i.e. from Menu „InP‟ the first sub menu is InP1.
6. Press and release the down button (▼) to select the required sub menu.
The sub menus are as follows
Menu
Sub Menus
InP
InP1
InP2
InP3
Cntr
CtyP
CACt
SPL
SPH
oLLo
oLHi
rAFC
FnCt
rASL
toLP
rAL
AF
FnCt
AL
HYSt
ACrA
OutP
FnCt
Si Gn
rOut
OPnt
End
BinF
bin1
bin2
diSP
diSU
diSL
tout
deCP
CodE
IntF
r485
7. Once the required sub menu has been selected press and release ‘ENTER’. The first parameter for that sub
menu and its current setting will be displayed i.e. for „InP1‟, the first parameter is „SEn1‟. Refer to "RWF55
Configuration (ConF) Level Parameters" table on page 47.
8. Press and release the down button (▼) to scroll through the various parameters within the sub menu.
9. Once the required parameter has been selected, press and release ‘ENTER’ the parameter i.e. SEn1‟ will
start flashing.
10. Press and release (▲) or (▼) to enter the value for the relevant parameter as shown in the „Factory Setting‟
column of the "RWF55 Configuration (ConF) Level Parameters" table on page 47.
11. Press and release ‘ENTER’ to accept the new setting.
12. Perform steps 9 11 for each parameter. When the last „Configuration Level‟ parameter has been set,
proceed to step 13.
13. Press and hold ‘ESC’ for more than 2 seconds. The display will revert to show the probe and set point
temperatures.

Related product manuals