Catalog No.: 2000.22N Effective: 12-1-07 Replaces: 10-15-03
Job:
Engineer:
Contractor:
Prepared By: Date:
Model:
EFFICIENT
82% thermal efficiency – highest of any atmospheric
boiler available today
THERMAL SHOCK PROOF
Twenty-year warranty against thermal shock damage
up to 150°F differential
Maximum operating temperature: 230°F
LIGHTWEIGHT
A floor load of 70 lbs./sq. ft. or less
HIGH RECOVERY
Cuts fuel costs substantially because the standby and
radiation losses normal to other boilers are eliminated
LOW WATER OPERATING TEMPERATURE
Operates with water temperature as low as 105°F
without condensing
Heat Exchanger
ASME Inspected and Stamped
160 PSIG
National Board Approved
Headers
Glass-lined Cast Iron – Standard
Bronze – Option A-1
Finned Tubing
Copper – Standard
Cupro Nickel – Option A-3
ASME Steel Tube Sheet
Silicone O-Rings
60 PSIG ASME Pressure Relief Valve
Temperature and Pressure Gauge
(Boiler)
Water Connections
Left Hand – Standard
Right Hand – Option A-6
Flow Configuration
Two-pass – Standard
Single-pass (Cast Iron Only)
Pump, Rear-mounted (Optional)
4.25” Impeller
4.7” Impeller
Controls
120V, 60Hz, 1 Ph Power Supply
120/24V Transformer
100% Pilot Shut-off/Lockout
Electronic, Intermittent Ignition (IID)
Pilot
High Limit Control, Manual Reset
Controls (cont.)
On/Off Switch
Flow Switch
Economaster II Pump Time Delay
Gas Control Train
Manual Main Gas Shut-off Cock
Main Gas Pressure Regulator
Redundant Safety Shut-off Valve
Control Valve
Firing Mode
On/off (H4)
Two-stage Firing (H3)
Four-stage Firing (H9)
Mechanical Modulation,
110-170°F (H5)
Mechanical Modulation,
150-210°F (H1)
Motorized Modulation (H2)
B-6000 (H6)
Fuel
Natural Gas
Propane Gas
Design Certified ANSI Z21.13/CSA 4.9
Construction
Front Controls
Stainless Steel Burners
Polytuf Powder Coat Finish
Stackless Top
Base (Optional)
Combustible Floor Shield – Option J-1
Temperature Controllers
Note: H1 and H5 do not require a controller
B-7 Modulating
B-5 Modulating, Outdoor Reset
B-6 Two-stage
B- Four-stage Digital
Y-241 Electronic Sequencer,
1-4 Stages
Y-281 Electronic Sequencer,
1-8 Stages
Additional Safety Controls
F-9 Low Water Cut-off Probe
I-1 High Limit Control,
Auto Reset
S-1 Low Gas Pressure Switch
S-2 High Gas Pressure Switch
Regulatory Agency Requirements
Raytherm
®
- Type H
Hydronic Heating Boilers
Commercial
Models 926-1758 (Outdoor)
Fig. #8953
Question and Answer IconNeed help?

Do you have a question about the Raypak Raytherm - Type WH 926-1758 and is the answer not in the manual?

Raypak Raytherm - Type WH 926-1758 Specifications

General IconGeneral
CategoryWater Heater
Model NumberWH 926-1758
BrandRaypak
SeriesRaytherm
Fuel TypeNatural Gas
Thermal Efficiency82%
First Hour RatingNot available
Minimum Water Pressure30 PSI
Maximum Water Pressure160 PSI
ModelRaytherm
TypeWH

Summary

Product Features

Efficient Operation

Features 82% thermal efficiency, the highest for atmospheric boilers.

Thermal Shock Proof

Twenty-year warranty against thermal shock damage up to 150°F differential.

Lightweight Design

Offers a floor load of 70 lbs./sq. ft. or less.

High Recovery

Cuts fuel costs by eliminating standby and radiation losses.

Low Water Operation

Operates with water as low as 105°F without condensing.

Component Specifications

Heat Exchanger Details

Details ASME construction, materials like cast iron or bronze, and fittings.

Control System Components

Includes power supply, transformer, pilot shut-off, and ignition system.

Gas Control Train

Specifies manual shut-off, pressure regulator, control valve, and firing modes.

Temperature Controllers

Lists available controllers like modulating and digital options.

Additional Safety Controls

Includes low water cut-off, high limit controls, and pressure switches.

Regulatory Agency Requirements

Lists design certifications and compliance standards.

Model Dimensions and Performance

Model Specifications

Details model numbers, MBTU input/output, dimensions, and connections.

Boiler Flow and Pressure Drop

Provides GPM and pressure drop data for two-pass and single-pass systems.