EasyManuals Logo

RCS TBZ48A User Manual

RCS TBZ48A
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
DCN: 140-02121-02 Page 6
Cooling Stage 1 OFF Delta (C1D OFF) Range: 0 to 6 degrees Default: 0
Sets the delta from setpoint that stage 1 cooling stops.
Stage 1 turns off at setpoint - Delta Stage 1
Cooling Stage 2 ON Delta (C2D ON) Range: 2 to 8 degrees Default: 2
Sets the delta from setpoint that stage 2 cooling starts.
Cooling Stage 2 OFF Delta (C2D OFF) Range: 0 to 7 degrees Default: 0
Sets the delta from setpoint that stage 2 cooling stops.
Stage 2 turns off at setpoint - Delta Stage 2.
Maximum Heat Setpoint (HSPMAX) Range: 55F to 96F (4C-43C) Default: 90F (32C)
Sets the maximum heating setpoint value.
Will not ramp or accept setpoints higher than this maximum.
Minimum Cool Setpoint (CSPMIN) Range: 60F to 99F (6C-45C) Default: 60F (15C)
Sets the minimum cooling setpoint value.
Will not ramp or accept setpoints lower than this minimum.
Minimum Run Time (MRT) Range: 1- 9 Minutes Default: 3
Sets the Minimum Run Time before a heating/cooling cycle can turn off.
Sets heating/cooling cycle time. Prevents rapid on/off cycling.
Minimum Off Time (MOT) Range: 5-9 Minutes Default: 5
Sets the Minimum Off Time before another heating/cooling cycle can begin. Provides
compressor short cycle protection.
Heat Fan Purge (H PURGE ) Range: 0-90 Seconds Default: 0
Runs the fan for this many seconds after the heat call ends. A value of 0 is OFF.
Cool Fan Purge (C PURGE) Range: 0-90 Seconds Default: 0
Runs the fan for this many seconds after the cool call ends. A value of 0 is OFF.
Status Line Display (STATUS) Range: SP (Setpoints), CL (Clock) Default: SP
Sets what is displayed on the status line of the main screen, either the Heat/Cool Setpoints
or the Clock Time.
Test Mode (TEST) Range: Y or N Default: N
Y= Test mode on. Reduces all delays to 10 sec for quicker system testing
N= Test mode off. Normal system delays
CAUTION: In test mode all system safety delays are shortened. Do not operate the
system compressor in test mode. Disconnect Y1 or Y2 outputs if using test mode
on a live system.
Restore Defaults (RESET) Range: Yes, No Default: No
Restores all settings to factory defaults.
Press Yes to restore defaults
Press No to exit and not restore defaults
System Type (SYSTYPE) Range: S or HP Default: S
Sets the HVAC System type, StandardGas/Electric (S) or Heat pump (HP)
Fan Type (FANTYPE) Range: G or E Default: G
Sets the HVAC Fan type, Gas (G) heat or Electric (E) heat.
Only for Standard HVAC systems, no fan for gas systems, always for electric.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RCS TBZ48A and is the answer not in the manual?

RCS TBZ48A Specifications

General IconGeneral
BrandRCS
ModelTBZ48A
CategoryThermostat
LanguageEnglish

Related product manuals