Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
35
11.4 Parameter settings 3. :
Parameter
Description
Settings
3.1
Select limit switches in case of
fire
NES:
1
.1 Use normal limit switch close to
additional limit switch (S6 off)
.2 Extra limit switch (S6) as "Overclose"
limit switch
.3 Use the normal limit switch close and
use additional limit switch (S6) as an end
switch (intermediate position) in case of
fire
DES:
.1 Use normal end position close as end
position close to fire
.2 “Overclose" end position as terminal
position close to fire
3.2
Automatic closing time when
using escape button when fire
1 t/m 240 seconds
1
sec.
3.3
Function normal open button
when fire
.1 Open button disabled
1
.2 Hold to run open when pressing and
immediately close again after releasing
3.4
BM function after BMC has
been active
0 t/m 140 seconds
0
sec.
3.5
Number of attempts activation
safety edge or photocell in case
of fire.
0 t/m 10 Attempts
0 = number of attempts infinitely.
0
3.6
Ignore underflow and/or photo
cell if it is not detected when
active BMC or RMC
.1 Enable roller shutter/door closes without
security
1
.2 Switching off roller shutter/door
remains open
3.7
Function at low battery voltage
.1 Only report
2
.2 Close shutter/door and report
3.8
Level low battery voltage in
Volt
20 t/m 25 Volt
22
3.9
Function of the safety edge
and/or photocell after reaching
the number of attempts.
(Parameter 0.4 > .1 and
parameter 3.5 > 0).
.1 Continue closing without safety edge
1
.2 Open and stop two seconds (only
possible if the mains power supply is still
present)
.3 Only stop (brake remains energized
until batteries have insufficient capacity
when mains power has failed)