Door control
FireProV2
Manual
Please keep this manual with attachments carefully!
34
11.3 Parameter settings 2. :
Parameter
Description
Settings
2.1
Motor duration
monitoring
1 t/m 240 seconds
120
sec.
2.2
Function pulse input
when selecting
parameter 0.1 on
automatic opening
.1 Cant stop in open direction
1
.2 Can stop in open direction
2.3
Automatically close
time with normal
operation.
0 = Disabled
1 t/m 240 seconds
0
2.4
Photo cell function
during countdown
automatically closes
time at normal
operation.
.0 Time restarts at photocell interruption
0
.1 After interruption photo cell, the door will
close after 3 seconds regardless of the time left
2.5
Number of re-openings
at automatic closing and
ratification underrun
1 t/m 10
2
2.6
Function potential-free
alternating contact RM
close
.1 RM close, reports at smoke detection door is
fully closed
1
.2 Reports that a fault notification is active
.3 Test function light curtain
2.7
Pre-warning for closing
at normal operation
0 t/m 60 Seconds
0
sec.
2.8
Pre-warning for closing
when fire, smoke or
empty battery
0 t/m 60 Seconds
0
sec.
2.9
Disable photo cell
function for certain
range (DES only )
.0 Off
0
.1 enable, teach twice reference position