EasyManua.ls Logo

RDM PR0029L-ACF - Page 5

RDM PR0029L-ACF
14 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Brooklands Case Controller | Document Revision 2.2c
www.resourcedm.com
5
Parameter
Range
Step
Units
Default
PR0029L
EEV
PR0029L/37
LLV
230V ACF
PR0029L/37
EEV
230V ACF
PR0033E
EEV
Evap Select
Local/ Remote
-
-
Local
Div Value
0 to 100
1
%
50
Ctrl Probe Type
Air Probe/
Logging
-
-
Air Probe
PWM
0 to 100
1
%
80
Valve Type
EEV/LLV
1
-
EEV
Co2 App
Off
Mode 1
Mode 2
1
-
Off
Alarm delay
00:00 to 99:00
01:00
mm:ss
20:00
Yellow UT Alarm
-49.0 to 60.0
0.1
Deg C
-3.0
Yellow OT Alarm
-49.0 to 60.0
0.1
Deg C
5.0
Red UT Alarm
-49.0 to 60.0
0.1
Deg C
-2.0
Red OT Alarm
-49.0 to 60.0
0.1
Deg C
6.0
Green UT Alarm
-49.0 to 60.0
0.1
Deg C
0.0
Green OT Alarm
-49.0 to 60.0
0.1
Deg C
12.0
Yel Prod UT Alm
-49.0 to 60.0
0.1
Deg C
-1.0
Yel Prod OT Alm
-49.0 to 60.0
0.1
Deg C
6.0
Red Prod UT Alm
-49.0 to 60.0
0.1
Deg C
0.0
Red Prod OT Alm
-49.0 to 60.0
0.1
Deg C
9.0
Grn Prod UT Alm
-49.0 to 60.0
0.1
Deg C
4.0
Grn Prod OT Alm
-49.0 to 60.0
0.1
Deg C
12.0
Defrost Start
00:00 to 23:50
00:01
hh:mm
01:00
Defrost Number
0 to 8
1
-
6
No Defrost Time
0 to 25
1
-
8
Def. term. temp.
-49.0 to 30.0
0.1
Deg C
8.0
Defrost min time
00:00 to 99:00
01:00
mm:ss
15:00
Defrost max time
00:00 to 99:00
01:00
mm:ss
45:00
Drain down time
00:00 to 24:00
00:15
mm:ss
01:30
Recovery time
00:00 to 99:00
01:00
mm:ss
30:00
Defrost Mode
Local/ Remote
-
-
Local
Fans in Def
Off/On
-
-
On
Lights Mode
Local/Remote/Ma
n Off/ Man On
-
-
Local