PendentUpright
Note: Not all versions of the product are shown.
Features
• Standard coverage, standard-response sprinklers
• Upright, pendent, horizontal sidewall, and vertical sidewall
deflectors
• Robust solder capsule thermal element
• Available in a wide variety of nishes
Product Description
Reliable Model G Series sprinklers are standard-response
standard spray automatic sprinklers using a solder capsule
thermal element. The solder is captured in the cylinder of the
capsule by a stainless steel ball. When the solder melts, the ball
moves into the cylinder allowing the thermal element to fall away
from the sprinkler. When this occurs, the compressed strut and
lever spring free from the sprinkler. System pressure then clears
the waterway of all operating parts allowing the deflector to
evenly distribute water.
Pendent and horizontal sidewall sprinklers may be installed
exposed or surface mounted using escutcheons such as the
Reliable Models B, C, or HB (reference Technical Bulletin 204).
When installed recessed, the Model G Series sprinklers are
specically listed with and may only be installed with listed
Reliable escutcheons. Refer to the technical information on the
following pages for specic listings for recessed installations and
Figures 6 and 7 for dimensional information.
www.reliablesprinkler.com
Model G Series
Standard-Response Sprinklers
Bulletin 110 January 2023
Sprinkler Summary
Model
K-Factor gpm/psi
1/2
(lpm/bar
1/2
)
Listings & Approvals Threads
Sprinkler Identication
Number (SIN)
G Upright
2.8 (40) UL, FM 1/2” NPT, ISO 7-R1/2 R1021
4.2 (60) UL 1/2” NPT, ISO 7-R1/2 R1023
5.6 (80) UL, FM, LPCB, EC, UKCA 1/2” NPT, ISO 7-R1/2 R1025
8.0 (115) UL, FM 1/2” NPT, ISO 7-R1/2 R1026
8.0 (115) UL, FM, LPCB, EC, UKCA 3/4” NPT, ISO 7-R3/4 R1027
G Upright
Intermediate
5.6 (80) UL, FM 1/2” NPT, ISO 7-R1/2 R1425
8.0 (115) UL, FM 3/4” NPT, ISO 7-R3/4 R1427
G Pendent
2.8 (40) UL, FM 1/2” NPT, ISO 7-R1/2 R1011
4.2 (60) UL 1/2” NPT, ISO 7-R1/2 R1013
5.6 (80) UL, FM, LPCB, EC, UKCA 1/2” NPT, ISO 7-R1/2 R1015
8.0 (115) UL, FM 1/2” NPT, ISO 7-R1/2 R1016
8.0 (115) UL, FM, LPCB, EC, UKCA 3/4” NPT, ISO 7-R3/4 R1017
G Horizontal
Sidewall
2.8 (40) UL 1/2” NPT, ISO 7-R1/2 R1231
4.2 (60) UL 1/2” NPT, ISO 7-R1/2 R1233
5.6 (80) UL, FM, LPCB 1/2” NPT, ISO 7-R1/2 R1235
8.0 (115) UL 1/2” NPT, ISO 7-R1/2 R1236
8.0 (115) UL 3/4” NPT, ISO 7-R3/4 R1237
G Vertical Sidwall 5.6 (80) FM, LPCB, EC, UKCA 1/2” NPT, ISO 7-R1/2 R1285
Table A
When tted with an approved water shield, these sprinklers may
considered intermediate sprinklers for use in racks, below grated
walkways, and other areas where intermediate level sprinklers are
required.