REMKO KWL (H)
46
Technical data
Series
KWL
130 H
KWL
160 H
KWL
180 H
KWL
220 H
KWL
270 H
KWL
320 H
KWL
370 H
Operating mode
Air-cooled compact chiller with heat pump function
and with the adaptive function for cooling and heating
Nominal cooling capacity
1)
kW 12,9 15,9 18,1 21,8 27,1 31,5 37,2
Nominal heating capacity
2)
kW 14,9 17,5 19,8 24,2 29,9 35,1 39,7
Energy efficiency ratio cooling EER
1)
2,42 2,59 2,57 2,56 2,67 2,67 2,65
Energy efficiency ratio heating COP
2)
2,53 2,60 2,58 2,70 2,80 2,78 2,71
Setting range return temp. Cooling °C +10 to +18
Setting range return temp. Heating °C +20 to +45
Operating range - cooling °C +5 to +45
5)
Operating range - heating °C -10 to +20
Operating range cooling (extension) °C -15 to +45
6)
Cooling circuits, number 1
Capacity scaling % 0 / 100
Refrigerant R 407C
7)
Max. operating pressure, refrigerant kPa 1900 / 2800
Compressor, number / type 1 / Scroll
Air flow rate, max. m³/h 9570 9740 10240 10240 11940 11720 16300
Sound pressure level
3)
dB(A) 48,2 48,2 48,7 48,4 48,5 48,6 51,3
Sound power level dB(A) 79,2 79,2 79,7 79,4 79,5 79,6 82,3
Power supply V / Hz 400/3~/50
Protection class IP 24
Elec. power consumption, max.
4)
kW 11,56 12,90 15,03 17,08 18,59 21,94 31,08
Elec. current consumption, max.
4)
A 16,69 18,62 21,70 24,66 26,83 31,67 44,86
Nom. electrical power consumption, cooling
1)
kW 5,33 6,13 7,04 8,51 10,16 11,81 14,02
Elec. nominal current consumption cooling
1)
A 11,45 12,77 16,04 16,96 19,54 22,35 30,06
Nom. electrical power consumption, heating
2)
kW 5,90 6,72 7,68 8,97 10,66 12,64 14,63
Elec. nominal current consumption
heating
2)
A 12,15 13,07 16,54 16,98 20,03 23,42 30,70
Elec. starting current, max. A 72 80 101 126 130 170 183
Operating medium max. 35% ethylene glycol; max. 35% propylene glycol
Operating limits, medium °C +4 to +50
Max. operating pressure, medium kPa 300
Nominal flow volume, medium C/H m³/h 2,23 2,74 3,10 3,74 4,64 5,44 6,41
Minimum flow volume, medium m³/h 1,40 1,80 2,00 2,40 3,00 3,50 4,10
Maximum flow volume, medium m³/h 3,40 4,50 5,20 6,20 7,80 9,00 10,70
Nominal pump pressure, max. kPa 207,0 195,0 188,0 177,0 162,0 145,0 175,0
Nominal pressure loss, internal cooling kPa 38,0 30,1 23,2 31,4 45,0 47,2 58,1
System pressure, available cooling kPa 169,0 164,9 164,8 145,6 117,0 97,8 116,9
Diaphragm expansion vessel, volume l 6,0
Diaphragm expansion vessel MAG, preliminary pressure
kPa 150
Medium connection, intake Inches 1 /1/4 indoors
Medium connection, outlet Inches 1 /1/4 indoors
Medium content, pipe lines l 2,1 2,5 3,1 3,7 4,2 4,8 6,4
Minimum medium volume, per unit l 40,0 47,0 51,0 62,0 80,0 91,0 104,0
Dimensions - height mm 1115 1215 1300 1300
width mm 430 520 620 1160
depth mm 1220 1420 1670 1535
Weight kg 170,0 176,0 268,0 285,0 325,0 332,0 398,0
Operating weight, approx. kg 172,1 178,5 271,1 288,7 329,2 336,8 404,4
Standard colour similar to RAL 9018 / INOX
Serial number INOX
1025... 1026... 1027... 1028... 1029... 1030... 1031...
EDP no. INOX
1650133 1650163 1650183 1650223 1650273 1650323 1650373
Serial number RAL 9018
911... 912... 913... 914... 915... 916... 917...
EDP no. RAL 9018
1650131 1650161 1650181 1650221 1650271 1650321 1650371
1) Air intake temperature TK 35°C, medium intake 12 °C, medium outlet 7 °C, 0% glycol concentration
2) Air intake temperature TK 7°C, medium intake 40 °C, medium outlet 45 °C, 0% glycol concentration
3) Distance 10 m free field
4) Air intake temperature TK 45°C, medium intake 18 °C, medium outlet 15 °C, 0% glycol concentration
5) Crank case heating compressor (standard equipment)
6) Only with winter pressure regulation accessory, set
7) Contains greenhouse gas according to Kyoto protocol