28
Parameters Number
Parameter Name Description
Set options
The range can be configured
between 0-40A
Supply for industrial frequency
transformer (disabled)
Supply for industrial frequency
transformer (enabled)
[28] 40A
(Default)
[29] DIS
(Default)
[29] ENA
28
29
35
36
37
Maximum AC
Charging Current
Supply For
Transformer(If the
output is connected
to a transformer )
Enable alarm prompts when the
status of the primary input source
changes
26
Mode Transition
Alarm
[26] ENA
(Default)
When disabled, the unit will not
transfer to Utility mode
When enabled, the unit will transfer
to Utility mode if overload occurs in
battery mode.
[27] DIS
[27] ENA
(Default)
27
Overload bypass:
When enabled, the
unit will transfer to
line mode if
overload occurs in
battery mode.
[35] 50.4V
(Default)
Set point that recovers and
reconnects the solar inverter from
being disconnected in Low Voltage
Disconnect. The range is from 44V
-58.4V, in 0.4V increments.
Low Voltage
Disconnect
Recover
[36] 80A
(Default)
Adjustable PV current settings.
The range is from 0 – 80A.
PV Charging
Current
[37] 52V
(Default)
When the battery reached at
floating status, it will need to be
lower than this setpoint before it
starts charging. The range is the
( Undervoltage Warning )~
( Floating Voltage – 1.2V )for the
respective battery
Battery Charging
Boost Return
Setpoint
38
[38]120Vac
default
Can set from
100Vac/105Vac/110Vac/120Vac.
The rated output power will be
reduced= (Power Rate)*(Vset/120)
AC output voltage
setting (only can
be set in the
standby mode )
39
[38]40A
default
Max AC input current. Setting
range: 0~40A.
(102% < current <110%): report
error and turn off the output after 5
minutes;
(110% < current < 125%) : report
error and turn off the output after
10 seconds;
current >125% : report error and
turn off the output after 5 seconds;
Max AC input
current setting