Data Setting
By pressing the SET button, the user is able to modify some parameters of the meter.
They include: Battery Amp-Hours (Ah) (4), Battery Temperature Compensation (5),
Battery Type (6), and Load Timer Mode (7). The user uses the (K2) () and (K3) () to
adjust the parameter, and then press (K1) SET again to save the setting.
The icon will be displayed when the user is in the SET function. It will disappear
once the user is in the reading menu.
NOTE: In the menu display above, you will see the screens with the adjustable
parameters because they will have the icon.
NOTE: The user uses the SET function to access the data setting parameter. A symbol
will appear by which the user utilizes the (K2) () and (K3) () to adjust the parameter,
and then press (K1) SET again to save the setting.
Battery Amp-hour ranges from 10Ah to 900Ah. The default value
will be 200Ah. Once the user presses the SET button, they will be
able to modify the Amp-hours in increments of 10Ah.
Battery Temperature Compensation
The data ranges from 0 to 10mV/Cell/°C. When the function is set
to 0, there will be no temperature compensation.
Choose from a sealed lead acid battery (SEL), a gel battery (GEL),
or a flooded battery (FLD).
This screen corresponds with the MPPT charge controller’s Timer 1
and Timer 2 option. The user is able to program the timer from the
MT-5 Tracer by choosing the number that corresponds to the
desired timer. This information can be found on the manual of the
MPPT Charge Controller.