Time period – switch-on condition
tDTO
Time period – switch-on condition
Adjustment range: 1 … 100 s
Factory setting: 60 s
The parameter tDTO is used for adjusting the time period during which the
switch-on condition must be permanently fullled.
Filling time
tFLL
Filling time
Adjustment range: 1.0 30.0 min
Factory setting: 5.0 min
The parameter tFLL is used for adjusting the lling time. During this period, the
pump runs at 100 % speed.
Stabilisation
tSTB
Stabilisation
Adjustment range: 1.0 15.0 min
Factory setting: 2.0 min
The parameter tSTB is used for adjusting the time period during which the switch-
off condition will be ignored after the lling time has ended.
Operating mode
MAN
Operating mode
Adjustment range: OFF, Auto, On
Factory setting: Auto
For control and service work, the operating mode of the relays can be manually
adjusted. For this purpose, select the adjustment value MAN in which the following
adjustments can be made:
• MAN
Operating mode
OFF : Relay off (ashing) +
Auto : Relay in automatic operation
ON : Relay on (ashing) + + /
Note
Always adjust the operating mode back to Auto when the control and
service work is completed. Normal operation is not possible in manual
mode.
Language
LANG
Language selection
Selection: dE, En, Fr, ES, It
Factory setting: dE
In this adjustment channel the menu language can be selected.
dE : German
En : English
Fr : French
ES : Spanish
It : Italian