15
Tubing
INSTALLATION
Interconnecting Tubing (cont�)
For applications that are considered to have a long
line set with the outdoor unit and indoor unit on the
same level the following is required:
TXV or EEV on the indoor unit
Start components may be required depending
upon quality of voltage (consistently <200vac at
outdoor unit)
Crankcase heater (Some models have factory
installed CCH's� Refer to tables on pages 13 and
14�)
Insulated liquid and suction line in unconditioned
space only
Vapor line should slope toward the indoor unit
Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments
spelled out in this document and the outdoor
units I&O
Verify at least 5°F sub-cooling at the ID unit prior
to throttling device
ST-A1219-02-02
OUTDOOR UNIT BELOW INDOOR SECTION LINE SET
ROUTE
REFIGERANT LINES
EVEN WITH TOP OF
COIL OR INSTALL
INVERTED TRAP.
INSULATE
LIQUID AND
SUCTION LINE
REFERENCE TABLE 2 FOR
MAXIMUM LENGTH
LIMITATIONS
For applications that are considered to have a long
line set with the outdoor unit below the indoor unit
the following is required:
TXV or EEV at the IDunit
Crankcase heater (Some moels come with factory
installed CCH's� Refer to tables on page 13 & 14�)
Start components may be required depending
upon quality of voltage (consistently <200vac at
outdoor unit)
Refrigerant lines should be routed even with the
top of the ID coil or an inverted trap is to be ap-
plied. (Reference gure 4).
Insulated liquid and suction line in uncondi-
tioned space only
Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments
spelled out in this document and the outdoor
units I&O
Measure pressure at the liquid line service valve
and prior to expansion device� Verify that it is
not greater than 50 PSI
For elevations greater that 25’ can expect a
lower sub-cooling
Figure 4