29
Dual 7-Segment
LEDs Display
Code
Diagnostic Description
Status/Possible Cause Troubleshooting
Information
29 – High Pressure Control Open
The ICC detects the HPC is open
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
29L Active Protection High Pressure
Control Trip
LPC has opened 3 times in the same cooling
operation, the ICC has locked out the compressor
to protect it. ICC alternately flashes L and 29
FLASHING
83 – Condenser Coil Temperature Fault
The sensor detects an abnormally low or
high coil temperature
Replace the sensor
Check sensor is installed correctly on control
84 – Outdoor Ambient Temperature Fault
The sensor detects an abnormally low or
high outdoor ambient temperature
Check unit placement – If the outdoor unit is in
a high temperature area, wait until the ambient
temperature drops and check sensor reading.
Replace the sensor.
Check sensor is installed correctly on control
93 – Internal Control Fault
The control is not functioning
properly.
Check control for proper system
operation.
Replace control
d1 – No Shared Data Replace memory card with correct system
information.
No Voltage Compressor
Welded Relay
• Check to ensure power to compressor is correct
• Check system to ensure proper operation
• Check capacitor
INSTALLATION

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem RA17 Series and is the answer not in the manual?

Rheem RA17 Series Specifications

General IconGeneral
BrandRheem
ModelRA17 Series
CategoryHeat Pump
LanguageEnglish

Related product manuals