AIR COOLED
CONDENSING UNITS
92-104921-07-06 (4/18)
Printed in USA
[ ] indicates metric conversions.
Do not destroy this manual.
Please read carefully
and keep in a safe place
for future reference by a
serviceman.
WARNING
THESE INSTRUCTIONS
ARE INTENDED AS AN AID
TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR
PROPER INSTALLATION,
ADJUSTMENT, AND
OPERATION OF THIS
UNIT. READ THESE
INSTRUCTIONS
THOROUGHLY
BEFORE ATTEMPTING
INSTALLATION OR
OPERATION. FAILURE
TO FOLLOW THESE
INSTRUCTIONS MAY
RESULT IN IMPROPER
INSTALLATION,
ADJUSTMENT, SERVICE,
OR MAINTENANCE
POSSIBLY RESULTING IN
FIRE, ELECTRICAL SHOCK,
PROPERTY DAMAGE,
PERSONAL INJURY, OR
DEATH.
INSTALLATION INSTRUCTIONS
RA17 MODEL SERIES 17 SEER
WARNING:
RECOGNIZE THIS SYMBOL
AS AN INDICATION OF
IMPORTANT SAFETY
INFORMATION
FEATURING INDUSTRY STANDARD
R-410A REFRIGERANT

Table of Contents

Questions and Answers

  • H
    Harry HallAug 17, 2025
    What to do if my Rheem Heat Pump unit will not run?
    • K
      Kristy GlennAug 17, 2025
      If your Rheem Heat Pump unit isn't running, several factors could be at play. Start by checking for correct voltage at the line voltage connections in the condensing unit. Also, make sure that the thermostat isn't out of calibration or set too high. Inspect the control board diagnostic codes. Look for blown fuses or tripped breakers and replace/reset them as needed. Check the transformer wiring and replace the transformer if it's defective. Reset the high-pressure control if it's open, and also refer to the high head pressure remedy. Do the same for the low-pressure control. Finally, verify the communication wiring if there's miswiring or the communication light is continuously on.
  • R
    Rebecca GriffithAug 20, 2025
    Why is my Rheem RA1760AJ2CB Heat Pump compressor short cycling?
    • T
      Tyrone CarterAug 20, 2025
      If your Rheem Heat Pump's compressor is short cycling, it could be due to several reasons. First, check the voltage at the compressor terminals to ensure it's within ±10% of the nameplate marking when the unit is operating. A defective overload protector could also be the culprit, so consider replacing it. Finally, refrigerant undercharge can cause short cycling, so adding refrigerant may solve the issue.
  • M
    Mark MaddenAug 22, 2025
    What causes insufficient cooling in my Rheem RA1760AJ2CB Heat Pump?
    • D
      Derek LevyAug 23, 2025
      Insufficient cooling in your Rheem Heat Pump can stem from several causes. The unit might be improperly sized, requiring a recalculation of the load. Improper indoor airflow could be the issue; it should be approximately 400 CFM per ton. An incorrect refrigerant charge can also lead to this problem, so charge the unit per the procedure attached to the service panel. Air, non-condensables, or moisture in the system necessitate recovering the refrigerant, evacuating, and recharging, along with adding a filter drier. A bad ID could also be the cause, in which case it should be replaced.
  • M
    Mary HolmesAug 26, 2025
    Why is my Rheem RA1760AJ2CB's outdoor fan running, but the compressor isn't?
    • T
      Todd KingAug 26, 2025
      If the outdoor fan is running but the compressor isn't in your Rheem Heat Pump, it could be due to a defective run or start capacitor, which would need replacement. Another possibility is a defective contactor, which should also be replaced. Check for correct voltage at the compressor and ensure all connections are secure. If the compressor is stuck, grounded, has an open motor winding, or an open internal overload, wait at least 3 hours for the overload to reset; if it remains open, replace the compressor. A low-voltage condition might also be the cause, in which case you should add start kit components.
  • A
    Andres GrahamAug 28, 2025
    What causes high head and high or normal vapor pressure in cooling mode on my Rheem RA1760AJ2CB?
    • D
      donaldconleyAug 28, 2025
      High head pressure along with high or normal vapor pressure in cooling mode on your Rheem Heat Pump can be attributed to a dirty outdoor coil, which needs cleaning. It could also be due to refrigerant overcharge, requiring a correction of the system charge. If the outdoor fan isn't running, repair or replace it. The issue might also arise from air or non-condensables in the system, necessitating refrigerant recovery, evacuation, and recharge.
  • M
    Madeline DouglasAug 31, 2025
    What causes low vapor, cool compressor, and iced indoor coil in my Rheem RA1760AJ2CB Heat Pump?
    • F
      Frances ButlerAug 31, 2025
      A low vapor pressure, cool compressor, and iced indoor coil in your Rheem Heat Pump can be caused by low indoor airflow. Increase the blower speed or reduce restrictions and replace the air filter. Operating below 65°F outdoors can also cause this issue, so add a Low Ambient Kit. Moisture in the system requires refrigerant recovery, evacuation, recharge, and the addition of a filter drier. Finally, a closed ID circuit necessitates repairing or replacing the ID coil.
  • K
    Kayla OrozcoSep 2, 2025
    Why do the registers sweat on my Rheem Heat Pump?
    • S
      Stephen MartinezSep 2, 2025
      Registers sweat on your Rheem Heat Pump due to low indoor airflow. To resolve this, increase the speed of the blower or reduce any restrictions. Also, replace the air filter.
  • J
    Jack WareSep 5, 2025
    What causes fluctuating head and vapor pressures in my Rheem RA1760AJ2CB?
    • J
      Jessica ThomasSep 5, 2025
      Fluctuating head and vapor pressures in your Rheem Heat Pump can occur if the = is hunting. Check the thermistor to vapor line connection. Air or non-condensibles in the system can also cause this issue, requiring refrigerant recovery, evacuation, and recharge.
  • T
    tracy90Sep 8, 2025
    What causes high vapor pressure in my Rheem Heat Pump?
    • P
      pauljohnsonSep 8, 2025
      High vapor pressure in your Rheem Heat Pump can be caused by an excessive load. Recheck the load calculation. A defective compressor can also be the problem, requiring replacement.
  • E
    edwardstabithaSep 12, 2025
    What causes high head and low vapor pressures in my Rheem RA1760AJ2CB Heat Pump?
    • M
      Molly DavisSep 12, 2025
      High head pressure and low vapor pressures in your Rheem Heat Pump can be caused by a restriction in the liquid line, expansion device, or filter drier. To resolve this, remove or replace the defective component. A bad = can also cause this issue; verify the thermistor and pressure transducer connection and operation.

Summary

Important Safety Information

Safety Warnings and Precautions

Details critical safety warnings, cautions, and necessary precautions for proper installation and operation.

Installation

Condensing Units with EcoNet Control

Introduces the EcoNet enabled 2-Stage Control System and its board components.

EcoNet Control Operation Modes

Details system operation modes like cooling stages, anti-short cycle timer, and compressor/fan delays.

Active Compressor Protection Modes

Describes protection modes for compressor faults like low/high pressure, protector trips, and locked rotor.

Active Protection Lockout and Recall Modes

Explains how to exit protection lockouts and enter/use test and fault recall modes.

ICC Control Operation with Conventional Wiring

Explains ICC operation using conventional thermostats, including start-up, cooling modes, and protection.

ICC Control Operation: Protection and Reset

Details compressor protection modes, lockouts, and methods for resetting the ICC control.

Test and Fault Recall Mode Operations

Guides on entering and utilizing Test Mode and Fault Recall Mode for diagnostics and system checks.

Electrical Wiring Installation

Covers power wiring, grounding, and control wiring requirements, including voltage ranges.

Start-Up

Initial Start-Up and Airflow Checks

Covers initial start-up procedures, crankcase heater energization, and verifying proper system airflow.

Evacuation and Leak Testing Procedures

Details the critical evacuation process and final leak testing steps for system integrity.

Refrigerant Charge Verification and Charging

Guides on checking charge, using R-410A, confirming airflow, and calculating charge by weight.

Refrigerant Charge Adjustment Methods

Explains gross charging by pressures and final charge adjustment using subcooling methods.

Installation Finishing and Charge Chart

Covers final installation steps, pressure-temperature charts, and charge adjustment guidelines.

Diagnostics

Electrical Troubleshooting Flowchart

A step-by-step flowchart to diagnose electrical issues preventing unit operation.

Rheem RA1760AJ2CB Specifications

General IconGeneral
Model NumberRA1760AJ2CB
BrandRheem
CategoryHeat Pump
HSPF Rating9.5
Refrigerant TypeR-410A
Voltage208/230
Phase1
Compressor TypeScroll