INSTALLATION
ICC Diagnostic Codes
Descriptions of the ICC diagnostic codes are provided below:
ECONET COMMUNICATION SYSTEM™ CONTROL WIRING
AND
CONVENTIONAL THERMOSTAT WIRING
ICC DIAGNOSTIC CODES
Dual 7-Segment
LEDs Display
Code
Diagnostic Description
0 – Standby
No command for unit operation
c - First Stage Cooling
Unit has received a command for first stage
cooling
Normal operation
c - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for first stage
cooling during an active anti-short cycle timer
or minimum run timer.
Wait until unit timer has expired or press the
TEST button to defeat short cycle delay.
C - Second Stage Cooling
Unit has received a command for second
stage cooling
Normal operation
C - Anti-short cycle timer (3 minutes) or
Minimum run timer (30 seconds) active
The unit has received a command for second
stage cooling during an active anti-short cycle
timer or minimum run timer.
Wait unit timer has expired or press the TEST
button to defeat short
cycle delay.
Status/Possible Cause Troubleshooting
Information
FLASHING
FLASHING
P – Protector Trip
A command for compressor operation is
present but no current is measured to the
compressor
Motor protector open
Line volta e disconnected
01 – Long Run Time (Compressor)
The compressor has continuously run for
more than 18 hours in the cooling mode.
Low refrigerant charge
Air ducts have substantial leakage
Dirty indoor air filter
Dirty outdoor coil
02 – High Side Fault
Compressor limit has opened four (4) times
within a call for operation
Outdoor coil is dirty (cooling mode)
Outdoor fan is not running (cooling mode)
Dirty indoor coil or filter (heating mode)
Indoor blower is not running (heating mode)
Liquid line restriction
Excessive refrigerant charge
03 – Short Cycling
The ICC detects the run time for the past
four (4) compressor cycles is less than three
(3) minutes each.
Check thermostat wire connections (R, C, 1, &
2)
Check thermostat location in zone (too close to
discharge grill)
Normal operation