Rheem Raypak 4450 - User Menu Settings; Basic User Settings; Pump Period Configuration

Rheem Raypak 4450
54 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
Item Range
Default
Value
Access
Level
Description
Set Current
Time
12:00A–11:59P User
Selects current time – “A” or “P” will indicate
whether the set time is AM or PM.
C/F Display Celsius/Fahrenheit Fahrenheit User
Selects the units of measure for temperature
readings.
Spa Max
Temp
65°F–104°F
(18°C–40°C)
104°F
(40°C)
User
Selects the maximum Spa temperature that
the control can be adjusted to in normal
operation.
Pool Max
Temp
65°F–95°F
(18°C–35°C)
95°F
(35°C)
User
Selects the maximum Pool temperature that
the control can be adjusted to in normal
operation.
Pump
Periods
0–4 User
Only available if Pump Operation in the
Installers Menu is set to “4-Speed Enabled” or
“Variable Enabled”.
Pump On Time 1 12:00A–11:59P User
Select ON time for Pump Period #1 to take
e󰀨ect.
Pump O󰀨 Time 1 12:00A–11:59P User Select OFF time for Pump Period #1 to stop.
Pump Speed 1
1–4 if 4-Speed
Enabled
0%–100% if Variable
Enabled
User
On 4-speed pumps, this denotes the selected
pump output (which connects to the pump for
the selected speed) for this pump period. On
variable-speed pumps, this denotes the PWM
signal to be provided to the pump for pump
operation.
Return Valve 1 Pool/Spa Pool User
Select the position of a 3-way valve located
between the heater and the Pool/Spa for this
scheduled pump period.
Suction Valve 1 Pool/Spa Pool User
Select the position of the 3-way valve located
between the Pool/Spa and the Pump for this
scheduled pump period.
Pump On Time 2 12:00A–11:59P User
Select ON time for Pump Period #2 to take
e󰀨ect.
Pump O󰀨 Time 2 12:00A–11:59P User Select OFF time for Pump Period #2 to stop.
Pump Speed 2
1–4 if 4-Speed
Enabled
0%–100% if Variable
Enabled
User
On 4-speed pumps, this denotes the selected
pump output (which connects to the pump for
the selected speed) for this pump period. On
variable-speed pumps, this denotes the PWM
signal to be provided to the pump for pump
operation.
User Menu – Heat Only, Power Defrost and Heat/Cool Models
NOTE: The User Menu is exactly the same for Heat ONLY, Power Defrost and Heat/Cool models.
NOTE: Make sure that the values for each setting are recorded for future reference or if the control ever needs to be
reset to Factory Defaults. All these values will need to be re-entered.
(Continued on next page)
Table D. USER MENU – Heat ONLY, Power Defrost and Heat/Cool Models