42
WATER OU
(TO POOL
OR SPA)
CHEMICAL
INTRODUCTION
CHECK
VALVE
FILTER
TER IN
O POOL
A)
Figure 14. Plumbing Schematic – External Bypass (Plumb the heater AFTER the lter and before any chlorinators.)
NOTE: Models 2450-4450 – For systems with pumps of 1-1/2 HP or greater (over 40 GPM / 151 LPM)
Models 5450-8450 – For systems with pumps of 2 HP or greater (over 80 GPM / 303 LPM)
External bypass required. Adjust the bypass valve to divert a minimum of 20 GPM / 76 LPM (2450-4450)
or 30 GPM / 114 LPM (5450-8450) through the heat pump pool heater.