82
3. Connect the wires coming from the power
source and the external device, following these
guidelines. See Figure 152 for further clarification.
a. If the application requires less than 3 amps, the
terminal block on the Crosswind V control board can be
used to drive power to the external device.
b. For applications over 3-amps, use a field-supplied
relay rated to the amperage and voltage of your
application, connected in cascade to the Auxiliary
output of the heater. See Figure 153.
4. Ensure that you follow the wire gauge and wire length
requirements specified for the external device. Use
the appropriate power source for your application. If
you are using field-supplied relays, make certain that
the coil is rated for the voltage of the external power
source.
AUX1
AUX2
C2
NO2
NC2
C1
NO1
NC1
Heat Pump
Auxiliary Outputs
Remote
selector
harness
L
R
G
24V
SPA
POOL
WPS HL1 HL2 VNT
P6 P7 P8 P4A
AVIA Gas Heater
Remote selector – Pool
mode
<< 24 VAC signal <<
>> Pool mode selection >>
Use INSTALLER menu to
configure Auxiliary Output
mode as “Auxiliary Heat”
Configure the heater to
operate in Remote mode.
Figure 151. Example 3: Gas Heater Commanded as Auxiliary Heater
IN OUT IN OUTIN OUT IN OUT
+
_
AUX1
AUX2
C2
NO2
NC2
C1
NO1
NC1
Crosswind V auxiliary outputs
shall be used in cascade with a
field-supplied relay.
Power Supply
External On/Off device. Load
above 3 amps.
Figure 153. External Device Wiring to Auxiliary Output
AUX1
AUX2
C2
NO2
NC2
C1
NO1
NC1
+
_
Crosswind V auxiliary outputs
can be used directly.
External On/Off device. Load
under 3 amps. at 24VAC
Power Supply
Figure 152. Applications Under 3 Amps