INSTALLATION
Interconnecting Tubing (cont�)
For applications that are considered to have a long
line set with the outdoor unit and indoor unit on the
same level the following is required:
TXV or EEV on the indoor unit
Start components may be required depending
upon quality of voltage
Crankcase heater
Insulated liquid and suction line
Vapor line should slope toward the indoor unit
Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments
spelled out in this document and the outdoor
units I&O
Verify adequate sub-cooling at the ID unit prior
to throttling device
Inverted trap even with
top of the coil
Insulated liquid and
sucon line
Reference Table 2
for elevaon
limitaons
Figure 4
Indoor Unit Above Outdoor Coil
For applications that are considered to have a long
line set with the outdoor unit below the indoor unit
the following is required:
TXV or EEV at the IDunit
Crankcase heater
Start components may be required depending
upon quality of voltage
Inverted vapor-line trap (Reference Figure 3)
Insulated liquid and suction line
Follow the proper line sizing, equivalent length,
charging requirements, and oil level adjustments
spelled out in this document and the outdoor
units I&O
Measure pressure at the liquid line service valve
and prior to expansion device� Verify that it is
not greater than 50 PSI
For elevations greater that 25’ can expect a
lower sub-cooling
Figure 4
Tubing