Rheem RTGH-RH10DV - Er:20 High Limit Switch Abnormality

Rheem RTGH-RH10DV
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58
Errorcode Meaning Condition
HighLimitSwitchAbnormality
(Manualrestore)
WhentheHighLimitSwitch
temperatureisoverheated,error
code20willappear.
Failureevent
AnEr.20willdisplayifthetemperatureoftheheatingwaterexitingtheprimaryheatexchangerexceeds
theHighLimitSwitch'sdefaultsettings.Combustionwillstopandthefanwillcontinuetorunforpost-
purge.
Checkpoint
①InspecttheHighLimitSwitchwhenerrorcodeappearseven
iftheheatingsupplytemperatureisnottoohigh.
②Checkconnectorandifnoproblem,measureHighLimit
Switchlocatedatheatexchangeroutletandreplacewhenthe
multi-metervalueshows'0L'.(Normalvalueis'0~0.5Ω'.)
(CN11:red⑧,⑯)
③Checkthecirculationpumpspeedsettingasspeed.
Chapter4Troubleshooting
HighLimitSwitch
(203℉/95℃)
1
2
3
4
5
6
9
10
11
12 13
7
14 15
8
16