Rheem RTGH-RH11DV - Chapter 4: Troubleshooting - Inlet Temperature Sensing; Er:31 DHW Inlet Thermistor Error

Rheem RTGH-RH11DV
98 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60
Errorcode Meaning Condition
DHWInletThermistorOpen
orShortCircuit
(Automaticrestore)
WhennoresponseatDHW In-
letThermistor,errorcode31will
appear.
Failureevent
When DHWInletThermistor’swiringlinelocatedatDHWInletconnectionisdisconnected.
Checkpoint
①VerifythattheDHWInletThermistorisproperlysecured
inthecoldwaterconnection.Verifyproperconnectionof
theDHWInletThermistor'swiringtothecircuitboard.
(CN7:blue
,blue
)
②MeasureresistanceacrosstheDHWInlet
Thermistorwithamulti-meter.Ifthemulti-meter
displays0Ω(shortcircuit),replacetheDHWInlet
Thermistor.
Chapter4Troubleshooting
DHWInlet(blue/blue)